Permit: T01CM05253

Parcel: 117120310

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM05253

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK FINAL.
03/19/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
02/27/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE PROVIDE MANFACTURES APPROVED FILLER BLANKS AT MAIN SWITCHBOARD. 2.) JUNCTION BOX COVERS ARE MISSING. 3.) WE HAVE COPPER PIPEING LAYING AGAINST EMT CONDUIT PLEASE INSULATE 4.) PLEASE BOND 18" X 18" JUNCTION BOX. 5.) A LETTER ON COMPANY LETTER HEAD IS NEEDED VERIFYING TORQUE VALVES 6.) PLEASE SUPPORT FLEX A SMOKEY FIRE ALARM #1&3 PREVIOUS INSPECTION.
02/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) SUPPORT FIRE/SMOKE DETECTOR BOXES WITH SUPPORT WIRES 2.) PLEASE THIGHTEN LOOSE FITTINGS AT PANELS. 3.) SUPPORT FLEX CONDUIT AS PER CODE 350-18 4.) BONDING DEVICES ARE NEEDED AT CT CAV 250-94. 5.) PLEASE IDENTIFY GROUDNING CONDUCTORS IN CT CAN 6.) 18" X 18" JUNCTION BOX NEEDS BONDING 250-96 7.) THE FILLER BLANKS AT THE MAIN SWITCH BOARD ARE TO BE MANUFACTURE APPROVED. 8.) PLEASE HAVE ELECTRICAN PRESENT TO OPEN UP SERVICE EQUIPMENT. 9.) PLEASE PROVIDE METER VERIFYING TORQUE VALVES.