Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05253
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK FINAL. | |
03/19/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
02/27/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE PROVIDE MANFACTURES APPROVED FILLER BLANKS AT MAIN SWITCHBOARD. 2.) JUNCTION BOX COVERS ARE MISSING. 3.) WE HAVE COPPER PIPEING LAYING AGAINST EMT CONDUIT PLEASE INSULATE 4.) PLEASE BOND 18" X 18" JUNCTION BOX. 5.) A LETTER ON COMPANY LETTER HEAD IS NEEDED VERIFYING TORQUE VALVES 6.) PLEASE SUPPORT FLEX A SMOKEY FIRE ALARM #1&3 PREVIOUS INSPECTION. | |
02/25/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) SUPPORT FIRE/SMOKE DETECTOR BOXES WITH SUPPORT WIRES 2.) PLEASE THIGHTEN LOOSE FITTINGS AT PANELS. 3.) SUPPORT FLEX CONDUIT AS PER CODE 350-18 4.) BONDING DEVICES ARE NEEDED AT CT CAV 250-94. 5.) PLEASE IDENTIFY GROUDNING CONDUCTORS IN CT CAN 6.) 18" X 18" JUNCTION BOX NEEDS BONDING 250-96 7.) THE FILLER BLANKS AT THE MAIN SWITCH BOARD ARE TO BE MANUFACTURE APPROVED. 8.) PLEASE HAVE ELECTRICAN PRESENT TO OPEN UP SERVICE EQUIPMENT. 9.) PLEASE PROVIDE METER VERIFYING TORQUE VALVES. |