Permit: T01CM04894

Parcel: 128010010

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM04894

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2001 ELECTRIC - INTERMEDIATE Approved
11/19/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*TRIM OUT PARTIAL
11/15/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
11/05/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) BACKWALLS ROUGHED IN OK.
11/02/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*THE MC CABLE MUST BE SECURED TO THE CENTER OF THE STUDS SO THAT THERE IS NOT LESS THAN 1 1/4" DISTANCE FROM THE FACE OF THE STUD TO THE MC. YOU MAY ALSO REMEDY THIS INSTALLING "NAIL PLATES".THANKS RECALL WHEN CORRECTED.
10/26/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PARTIAL 1.) SIDEWALLS NORTH & SO. ROUGH-IN.