Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/03/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
1.) RECEPTACLE IN RM 125 EACH WALL BOX BUT NO WIRE CIR EMLS 24. 2.) RECEPTACLE IN RM 128 LAST ONE ON CIR EMLS 28 HAS 1/2 EMT CONNECTOR WITH NOTHING IN IT REMOVE AND SEAL. 3.) WORK STATION WARMING RECEPTACLES MISSING RM 126 4.) RECP IN RM 127 MISSING. 5.) 4 RECEPTACLES CALLED FOR IN RM 129 SOUTH WALL NOT 3 6.) RM 130 MISSING RECEPTS ON WALL AND FLOOR BOX 7.) RM 131 MISSING RECEPT ON NORTH WALL 8.) PANEL LONG OUT IN RM BREAK NOT AS PER PLAN I DO NOT APPREA TO HAVE THE MOSE CURRENT PLANS HAVE SOME OF THE ABOVE ITEMS BEENS OMITTED OR REVISED? DAN SANTA CRUZ OFF TODAY CALL HIM TUES AM 791-5550 7-8AM OR RECALL INSPECTION SO HE CAN CHECK. |