Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 04/11/2002 |
ELECTRIC - UNDERGROUND |
|
Approved |
|
| 12/19/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*PERMETER CONDUIT FOR DOUBLE DUPLEX RECEPT. 4 RODES CORNER THERM WELD 2/0 B.C. 4 THERMO WELD TOPS |
| 11/28/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*CONCRETE ENCASEMENT WILL BE VERIFIED AT SUBSEQUENT INSPECTION THROUGH POT HOLE INSPECTION. |
| 11/15/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*FROM PANEL AREA TO 90 TURN 72 FT. APROX. APPROVED. 4-3/4"PVC CONDUITS NOW HAVE 3 1/2 QUARTER BENDS (4 IS MAX.). |