Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/20/2002 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/31/2002 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
FAN COIL 1.) NOTE CORRECT VOLTAGE MINUS ANY AUX. HT STRIP 2.) CONDENSATE AUX. DRAIN PAN W/ SEPERATE VENT LINE OR OVERFLOW IMC 307.2.3. 3.) NEED PERMANENT LIGHTS SOUTHEND FAN COIL. 4.) ID FAN COIL CONDENSER PERMANENT LABELS 5.) EXTERNAL DUCT INSUL. DO NOT ALLOW WRAP TO INPEED SMOKE/FIRE DAMPER ACTUATORS OR SMOKE ALARM UNITS. NOTE CORRECT FUSING ON CONDENSERS NOT 30 AMPS. NOTE SERVICE AREA ABOVE CORRIDOR EXISTING PENERATION IN FIRE RATED WALLS, NEED DIRECTION FOR SEALING AS NECESSARY EXISTING PENERTATION NOT MECHANICAL, WIRING BUNDLES ELECT. TRAYS ETCS. |