Permit: T01CM04408

Parcel: 126090650


Addresses:

129 N COLUMBUS BL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/22/2002 FRAMING Approved IVRS - Inspection 0000*
03/21/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) LARGE WOOLEY DOG IN REAR YARD, NO ANSWER AT FRONT DOOR, PLEASE RECALL
12/19/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE MUST HAVE TREATED SILL PLATE 2) MAXIMUM ALLOWED SPAN BETWEEN STUDS IS 16" 3) WINDOW AND DOOR HEADERS MUST BE SUPPORTED BY TRIMMER STUDS 4) 2 X HEADERS NOT ALLOWED TO BE INSTALLED IN THE FLAT 5) SILL PLATES MUST BE PROPERLY ANCHORED WITH 1/2" ANCHOR BOLTS AT 12" FROM ENDS OF SPLICES 6) REPLACED FIR POSTS CANNOT BE ENCASED IN CONCRETE 7) ALL BEAM SPLICES MUST BEAR ON STRUCTUAL MEMBERS 8) ORIGINAL BEARING WALL AT NORTH END OF ADDITION HAS BEEN REMOVED. 5 OR 6 RAFTERS OF ORIGNAL HOUSE AND PORCH ARE BEARING ON UNKNOWN STRUCTURE EXPOSE 9) REMOVE ALL DRYWALL ON ADDITION CEILING 10) THIS ADDITION IS ADDED LIVING SPACE. NOT STORAGE, REVISE PLAN 11) REVISE PLAN FOR ADDED ELECTRIC. YOU REQUIRE HEAT IN THIS AREA ALSO. YOU NEED A COMPLETE SET OF PLANS INCLUDING FIREPLACE