Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/13/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) ABS DWV OK WATER TEST OK 2.) COPPER WATER OK PRESSURE TEST OK 3.) GAS PIPING OK PRESSURE TEST OK 4.) OK TO COVER WALLS. |
| 01/10/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) REVIEW REQUIREMENT FOR WET VENTING. 2.) ABS PIECES NOT APPROVED SUPPORT.3.) EXTEND CLEAN OUT THRU WYE BRANCH 4.) TRAP FOR STAND PIPE RISER ROUGH ED TOO HIGH. 5.) SECURE 2 HOLE STRAPS TO STRUCTURE 6.) TRAP PRIMER REQUIRES VALVE AND UNION 7.) IF THE OWNER ONLY WANTS 2 CLOTHES WASHERS THATS FINE BUT THE APPROVED PLAN SHOWS 4 WASHERS AND MUST BE SIZED ACCORDINGLY. |