Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM03917
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) ABS DWV OK WATER TEST OK 2.) COPPER WATER OK PRESSURE TEST OK 3.) GAS PIPING OK PRESSURE TEST OK 4.) OK TO COVER WALLS. | |
01/10/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) REVIEW REQUIREMENT FOR WET VENTING. 2.) ABS PIECES NOT APPROVED SUPPORT.3.) EXTEND CLEAN OUT THRU WYE BRANCH 4.) TRAP FOR STAND PIPE RISER ROUGH ED TOO HIGH. 5.) SECURE 2 HOLE STRAPS TO STRUCTURE 6.) TRAP PRIMER REQUIRES VALVE AND UNION 7.) IF THE OWNER ONLY WANTS 2 CLOTHES WASHERS THATS FINE BUT THE APPROVED PLAN SHOWS 4 WASHERS AND MUST BE SIZED ACCORDINGLY. |