Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T01CM03917
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*1.) CONTRACTOR OBTAINED LETTER FROM ARCHETECT ALLOWING ABS IN LIEU OF PVC PVC DWV OK. WATER TEST OK. 2) INSPECTED PRE POUR OK FOR CONCRETE. | |
12/04/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*1.) I REVIEWED THE LETTER FROM THE ARCHECT ALLOWING ABS IN LIEU OF PVC.I FIND THIS ACCEPTABLE, HOWEVER, ALL CHANGES MADE TO THE PLAN MUST ALSO BE APPROVED BY THE CITY OF TUCSON PLAN REVIEWER, AND STAMPED APPROVED CROSSSING OUT A PIPE SIZE AND SUSITITUTING ANOTHER SIZE. IS NOT APPROVED. HAVE YOUR PLAN REVISED AND STAMPED, REFLECTING ALL CHANGES MADE TO THE PLAN. 2.) DRAIN FROM LOADING DOCK TO DAYLIGHT OK OK TO COVER. | |
12/03/2001 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION. | |
12/02/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*A. PLUMBING NOT INSTALLED PER PLAN 1.) BLDG SEWER MUST BE GRADED AT 2% 2.) READ NOTE #9 ON PLUMBING SCHEDULE MAT'1 TO BE SCH 40 PVC 3.) SEE DELTA ONE REVISION ON TOILET PLUMBING PLAN REQ'D 4" WASTE TO WASHERS ANY CHANGE TO PLAN MUST BE APPROVED. |