Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/01/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/29/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PROVIDE GREASE PANS UNDER EXHAUST FANS ON ROOF. 2.) PROVIDE MORE BANDING ON GREASE DUCT WRAP. 3.) INSTALL WASHER & WINGNUTS ON ACCESS DOORS. |
| 01/17/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1ST LAYER OF WRAP OK ON SYSTEM #3. INSPECTED 2ND LAYER OF WRAP ON SYSTEM 1 & 2. UP TO SOIL PIPE. OK FOR 3RD LAYER UP TO SOIL PIPE. OK FOR TEMP C OF O. |