Permit: T01CM03890

Parcel: 134082850

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/01/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) REVISED & APPROVED DRAWING FOR STUDOR VENT FOR KITCHEN SINK IS OK 2.) OK FOR DRYWALL.
10/31/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0000*SEE NOTES OF 10-17-2001
10/17/2001 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) WASTE & VENT SYSTEM IS OK 3.) OVERHEAD WATER DISTRIBUTION IS OK 4.) OK FOR DRYWALL UP TO KITCHEN PONY WALL ONLY. 5.) WILL REQUIRE A REVISED & APPROVED DRAWING FOR WASTE & VENT SYSTEM FOR KITCHEN SINK BEFORE NEXT INSPECTION.
10/10/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) FRONT UNIT KITCHEN SINK WASTE & VENT IS NOT TO CODE OR APPROVED PLAN 2.) TUB & SHOWER ENCLOSURES NOT INSTALLED A TIME BOTH UNITS 3.) CLOSET RINGS NOT INSTALLED @ THIS TIME BOTH UNITS 4.) KITCHEN SINK @ REAR UNIT HAS 1 1/2 STUBB OUT AND A 2" TRAP ARM. THE TRAP MUST BE THE SAME SIZE AS THE DRAIN IT SERVES 5.) C.O. FOR KITCHEN SINK @ REAR UNIT MUST BE @ VERTICAL OF HORIZONTAL AND MUST HAVE 12" OF CLEARANCE 6.) MUST TEST WASTE & VENT SYSTEM UP TO ROOF 7.) MUST SECURE ALL HORIZONTAL VENTS ABOVE CEILING. 8.) DID NOT MAKE CONNECTION OF HOT WATER FOR REAR RESTROOM LAY. FRONT UNIT.