| 11/06/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1.) CORRECTIONS MADE OK 2.) FINAL FOR MAINTENANCE BLDG. WILL BE GIVEN WHEN I REVIEW LETTER APPROVING THIN WALL IN LIEU OF SCH 40 ABS. 3.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. |
|
| 10/28/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE VERIFICATION OF GRADE ON SITE SEWER. 2.) PROVIDE CERTIFICATION ON RPPBP. 3.) 6" MINIMUM FROM TOP OF URINAL TO CRITICAL LEVEL ON URINAL FLUSHMETER. 4.) INSULATION KITS ON LAVATORIES ADA REQUIRES 18" FROM TO SIDEWALL HC WCLOSET. 15" FROM C TO SIDE WALL HC URINAL. |