Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/22/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) ABS DWV OK WATER TEST OK 2.) COPPER OK PRESSURE TEST OK 3.) OK TO COVER. |
| 07/12/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) I HAVE YET TO WITNESS A COMPLETE WATER TEST ON THIS BLDG. 2.) A HORIZOTAL EXTENSION OF A CLEAR-OUT SHALL BE MADE THROUGH A WYE BRANCH FITTING. 3.) REMINDER A TRAP SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED. |
| 07/01/2002 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) A VENT MUST BE INSTALLED LEVEL, OR SO DESIGNED TO DRAIN BACK TO THE FIXTURE IT SERVES. 2. OK TO COVER NON AFFECTED WALLS AND CEILINGS. |
| 06/20/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) SEE NOTE FROM 6/4/02 AND COMPLY. 2.) NO CORRECTION SINCE 6/7/02. 3.) PROVIDE VERIFICATION OF GRADE ON SEWER AS PREVIOUSLY REQUESTED 4.) CONTRACTOR TO PAY RE-INSPECTION FEE. |
| 06/07/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) WATER PIPING OK 2.) SEE NOTE 6/4/02. 3.) A TRAP ARM MAY NOT CHANGE SIZE 4.) A CLEAN OUT MAY NOT BE INSTALLED ON A HORIZONTAL. TRAP ARM. A SANTEE. MAY NOT LAY ON ITS SIDE. CORRECT AND RETEST. 5.) SUPPORT HORIZONTAL ABS. 6.) TEST ABS THRU ROOF 10' HEAD IS A SECTIONAL TEST ALL PIPING MUST BE TESTED. |
| 06/06/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/05/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/04/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*PLEASE IDENTIFY BUILDINGS & HAVE PLUMBER COMPLETE HIS WORK BEFORE CALLING FOR INSPECTION. |