Permit: T01CM03780

Parcel: 132042730


Addresses:

3225 E 44TH ST #02

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) EXTERIOR FIXTURES NEED TO BE 50 WATTS OR LESS PER LIGHTING ORDINANCE OR USE A SHOE BOX STYLE FIXTURE. 2.) PROPERLY FUSE COOLER MOTORS PER NEC. ( NOTE 15AMPS IS WAY OVER MAX. ALLOWABLE FUSING)