Permit: T01CM03780

Parcel: 132042730


Addresses:

3225 E 44TH ST #02

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
08/12/2002 ELECTRIC - UFER Approved IVRS - Inspection 0000*STEEL OF BUILDING IS 1ST SOURCE FOR GROUNDING ELECTRODE. THANKS MAC.
04/03/2002 ELECTRIC - UFER Partial Approval IVRS - Inspection 0000*1.) #2/0 ATTACHED TO REBAR OK TO POUR. 2.) PLAN & INSTALL OK RE WIRE SIZE FOR UFER.