Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/07/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/04/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) EXPOSED ROMEX/OF INFRONT OF BUILDING. 2.) LABEL DISCONNECTS, IDENTIFY CONDUCTORS, & SUPPORT SEALTITE - CHASE NIPPLE NOT APPROVED FITTING. 3.) MAKE UP FIXTURES AS PER MANUFACTURES INSTRUCTIONS. | |
| 12/30/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE CONNECT GROUNDING EQUIPMENT CONDUCTOR FOR BATH FIXTURE AND MAKE UP AND DIRECTIONS AS PER MANUFACTURE #1,,#3. 2.) SWITCHES TO BE GROUNDED AS PER CODE 380-9. 3.) I CAN NOT VERIFY IF FURANCE HAS THERMAL PROTECTION FOR MOTOR. IF NOT AND OVER CURRENT PROTECTION WILL NEED TO BE PROVIDED AT THE UNIT (SAU). 4.) PLEASE OPEN HOLE AT DISHWASHER/DISPOSAL PLUG FOR ACCESS ALL UNITS.5.) PLEASE PROVIDE FOR CLEANRENCE FO LIGHT FIXTURE IN CLOSET 410-8(1) 6.) A/C UNIT DISCONNECTS NEED TO BE LABELED 7.) EXPOSED ROMEX/UF IN FRONT OF BUILDING 8.) PLEASE PROVIDE ACCESS TO ROOF. |
|
| 12/17/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) INSTALL EXHAUST HOODS. 2.) NEED SRV AT FURNANCE 3.) FINISH ELECTRICA OK TEMP POWER FOR TESTING UNITS 1-4 | |
| 12/14/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) GFI RECEPTACLE UNDER SERVICE TO BE FIXED 2.) UNIT #1 KIT EXH FAN MISSING 3.) RECEP IN STORAGE RM MISSING 4.) BATH RM FIXS MISSING 2.) 1 KIT EX FAN MISSING BATH FIX'S MISSING, KIT LTS MISSING. PROCEED WITH TERMINATION THERE ARE TO MANY FIXTURES MISSING ( OPEN WIRING) TO RELEASE JUST YET OK TO CLOSE PANELS. | |
| 12/13/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*SUB PANELS NOT MADE UP AND YOU NEED TO COMPLETE DEVICES AND FIXTURES |