Permit: T01CM03750

Parcel: 11304299E

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/14/2001 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
09/13/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*1.) CONNECT RISER WITH A SECURE METHOD 1/4" HARDWARE MININUM 2.) CORRECT GROUNDING ELECTRODE CONDUCTOR TO GROUND CONDOCTOR OR PROVIDE MAIN BONDING JUMPER 250-24 3.) USE APPROVED FITTING TO CONNECT JUNCTION BOX ROMEX CONNECTORS & CHASE NIPPLES NOT APPROVED. 4.) DOUBLE LUGGING AT SERVICE 5.) TIGHTEN BOLTS FOR HUB. 6.) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE.