Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM03739

Parcel: 12213035B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/06/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
08/09/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* OK FOR TEMP C OF O
08/08/2001 MECHANICAL - FINAL Partial Approval PROVIDE AN OUTSIDE AIR VENT ON A/C 2. CONDENSATE DRAIN LINE ON AC Z DOES NOT HAVE ADEQUATE SLOPE. VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. PERMANENTLY LABEL EQUIPMENT ON ROOF W/SUITE NUMBER & UNIT NUMBER DO NOT USE INK. OK FOR TEMP C OF O.