Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/04/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*CONTR. REQUESTED AFTER HOURS INSP. SAT 8 AM 8/4/01 PAID CH #2149 $204.00 |
| 08/03/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) SUPPORT EMT CONDUIT PER ART 348 N.E.C. 2.) SUPPORT MC CABLE PER 334 N.E.C. 3.) DO NOT USE CEILING GRID WIRES INTENDED TO SUPPORT GRID TO SUPPORT ELECTRICAL RACEWAYS. 300 N.E.C. 4.) DONOT COVER CEILING TILL APPROVED BY INSPECTOR. 5.) DO NOT COVER WALLS BY LIGHT SWITCHES TILL MC IS MOVED 1 1/4" AWAY FROM FACE OF STUDS. 300-4 N.E.C. |
| 08/01/2001 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOTES: INSTALL CEILING FIXTURES & WIRING FOR INSPECTION. |