Inspection History Details
Permit: T01CM03651
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/31/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*BOND NEUTRAL BAR AT MAIN DISCONNECT. LINE AND LOAD TERMINATIONS REVERSED AT A/C DISCONNECT. |