Permit: T01CM03629

Parcel: 11307012A


Addresses:

1717 E GLENN ST 05

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/11/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*OK WALLS
04/08/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0950*PLEASE FINISH PREVIOUS INSPECTION AND RECALL.
04/07/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) SECURE SUB PANELS IN WALL.2.) TIGHTEN NM CABLE CLAMPS. 3.) PROTECT CABLE WHERE PASSING THROUGH STUDS 300-4. 4.) TIGHTEN CABLE CLAMPS AT BOXES IN RECESSED CANS AND LIGHT BOXES. 5.) NM CABLE ON OUTSIDE TO BE STRAPED WITHIN 12" OF EXISTING.
03/29/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*