Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/20/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) ABS DWV OK WATER TEST OK 2.) COPPER WTER OK PRESSURE TEST OK 3.) CLOSET FLANGES OK 4.) TUBS OK. 5.) OK TO COVER ALL AREAS. |
| 05/17/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*HANGERS AND SUPPORTS. |
| 05/16/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) HAVE COMPETENT PERSON WALK THROUGH AND CHECK ALL HANGERS AND SUPPORTS. |
| 05/15/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) HAVE COMPETENT PERSON WALK THROUGH AND CHECK ALL ANCHORS AND SUPPORTS. |
| 05/13/2002 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) NO TEST ON COPPER 2.) PROVIDE CLEVIS HANGERS AS NEEDED ON GAS LINE 3.) PROVIDE HANGERS ON ABS AS NEEDED 4.) SEE SPEC ON T.J.I NOTCHING DRILLING. |