Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 09/19/2001 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 09/14/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK EAST WALLS. |
| 09/04/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK WALLS OUTSIDE PERIMETER SOUTH WALL AND SOUTHEAST WALLS. |
| 08/27/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK WALLS OFFICE AREA. |
| 08/24/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) SUPPORT MC CABLE PER 334-10 N.E.C. AND JOB SPEC'S. 2.) NEED TO VERIFY INSTALLATION OF ANTI-SHORT. BUSHINGS ON MC CABLE AS NOTED LAST INSPECTION. 300-15 N.E.C. 110-12 N.E.C. 90-4 N.E.C. |
| 08/23/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*NOTES INSTALL BUSHING ON MC CABLE WHERE MORE THAN ONE CABLE TERMINATE INTO ONE CONNECTOR ( ANTI SHORT BUSHINGS.) |