Permit: T01CM03255

Parcel: 128010010

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM03255

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/09/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SEE NOT BELOW TRACK LIGHTING IS OK. THE CITED CODE ARTICLE & SUB SECTION REQUIRES THAT WHEN A CIRCUIT BREAKER IS BACK FED, THAT IS, WHEN THE LINE SIDE FEEDER FROM THE POWER SOURCE ( TRANSFORMER) IS FED INTO THE LOAD SIDE OF THE CIRCUIT BREAKER THE CIRCUIT BREAKER MUST BE SECURED TO THE BUSS OR MOUNTING RAIL WITH A SCREW OR BOLT TO PREVENT IT FROM CLN PLUGING FROM THE LOAD BUSS.
09/06/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK FOR TEMP C OF O. OK
1.) FOR FINAL INSTALL BACK ORDERED TALK LIGHTING 2.) ELECTRICIAN TO VERIFY THAT REVESE FED MAIN 100 AMP CIR BREAKER HAS A CLIP OR BOLT DOWN FEATURE 384-NEC 1999.
08/31/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*