Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK ROUGH ELECTRICAL |
| 05/14/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUND WIRE TO BE 3/4 OF A TURN AND NO MORE UNDER SCREW IN A CLOCKWISE DIRECTION. 2.) FILL ALL UNUSED OPENINGS IN BOXES 110-12. 3.) PLEASE FINISH WIRING WHAT IS 12-3 NM CABLE FOR 4.) PROTECT CABLE PASSING THROUGH STUDS 300-4. 5.) PLEASE INSTALL FLEX FOR AIR HANDLER AT ROUGH IN. PROTECT CABLE ENTERING FLEX CONDUIT. 6.) TIGHTEN BOX CLAMP ON 4/0 BOXES. |