Permit: T01CM03123

Parcel: 134082760


Addresses:

8301 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/31/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN
MADE FOR C OF O.
01/24/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) PROVIDE LISTING FOR RUBBER FLASHINGS ON B VENTS. 2.) PROVIDE MIDWEST BOX OR FUSE STAT FOR EVAP COOLER ELECTRICAL. 3) DRAIN LINES DONT HAVE ADEQUATE SLOPE. 4.) PROVIDE AN OUTSIDE AIR VENT ON AC UNIT 5.) RAISE B VENT 2' ABOVE EVAP COOLER 6.) FINISH HOOKING UP ELECTRICAL TO EQUIPMENT ON ROOF. 7.) AC EQUIPMENT NOT FUSED CORRECTLY. 8.) PROVIDE 1' CLEARANCE AROUND B VENTS. OK FOR TEMP C OF O.