Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/01/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/31/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*SEE NOTES PG. 2. CORRECTIONS REQUIRED 1.) A NON RAINTIGHT SWITCH (W/MISSING KNOCK-OUT) HAS BEEN INSTALLED ON THE ROOF. REPLACE WITH A RAIN TIGHT UNIT OR INSTALL SHEET METAL HOOD PERMANENTLY ATTACHED OVER THE SWITCH. 2.) EACH SWITCH MUST BE LABELED WITH PANEL NUMBER AND CIRCUITS OF PANEL OF ORIGIN.( E.G. PANEL "A" CKT 12 & 13.) 3.) COMPLETE THE WORK AND SECURE ALL CONDUIT, BOX COVERS ETC. |
| 01/25/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/25/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) COVER RECEPTACLES MUST BE WEATHER PROOF WITH PLUG IN 2. ONE RC UNIT ON ROOF TO BE FUSED AT 50 NOT 60A 3.) J-BOX ALL FRONT ENTRY FIXTURE 4.) OK FOR TEMP C OF O. FOR CHANGE OVER AND FIT UP. OK FOR TEMP C OF O FOR CHANGE OVER AND FIT UP EMPLOYEES TO OCCUPY ONLY NO PUBLIC SUBJECT TO OTHER INSPECTIONS. |