Permit: T01CM03123

Parcel: 134082760


Addresses:

8301 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/01/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/31/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*SEE NOTES PG. 2. CORRECTIONS REQUIRED 1.) A NON RAINTIGHT SWITCH (W/MISSING KNOCK-OUT) HAS BEEN INSTALLED ON THE ROOF. REPLACE WITH A RAIN TIGHT UNIT OR INSTALL SHEET METAL HOOD PERMANENTLY ATTACHED OVER THE SWITCH. 2.) EACH SWITCH MUST BE LABELED WITH PANEL NUMBER AND CIRCUITS OF PANEL OF ORIGIN.( E.G. PANEL "A" CKT 12 & 13.) 3.) COMPLETE THE WORK AND SECURE ALL CONDUIT, BOX COVERS ETC.
01/25/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
01/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) COVER RECEPTACLES MUST BE WEATHER PROOF WITH PLUG IN 2. ONE RC UNIT ON ROOF TO BE FUSED AT 50 NOT 60A 3.) J-BOX ALL FRONT ENTRY FIXTURE 4.) OK FOR TEMP C OF O. FOR CHANGE OVER AND FIT UP. OK FOR TEMP C OF O FOR CHANGE OVER AND FIT UP EMPLOYEES TO OCCUPY ONLY NO PUBLIC SUBJECT TO OTHER INSPECTIONS.