Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02712
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) INSTALL 15 AMP FUSES ON WALK IN 2.) INSTALL CORRECT COVER ON THERMOSTAT. | |
08/07/2001 | ELECTRIC - FINAL | Partial Approval | 1.)LABEL MAIN PNL. W/#S DESIGNATED ON PLANS 2.) LABEL MAIN PNL CIRCUIT BREAKERS 3.) LABEL WALK IN BO X COMPRESSOR DISCONNECT SWITCH. 4.) INTERIOR OF WALK IN FREEZER-A. MAIN FAN PULL OUT FUSE DISCONNECT MUST BE REPLACED OR REPAIRED AND FUSES INSTALLED. 5.) THERMOSTAT SWITCH NEEDS COVER. 6.J-BOX NEEDS BLANK COVER. |