Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 09/28/2001 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 09/26/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* |
| 09/24/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF UFER GROUND INSPECTION BY CITY OF TUCSON INSPECTION OR INSTALL 2 EACH GROUND RODS 8 FEET LONG AT LEAST 6' APART CONNECTED TO SERVICE 2) PANEL WITH A CONTINOUS #4 WIRE 3) ELECTRIC RISER REQUIRES A BONDING BUSHING AND BOND WIRE. LOCK NUT NO LONGER ALLOWED FOR BOND SEE N.E.C. 250-94 |