Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/03/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. |
| 08/02/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*INSTALL FUSES IN DISCONNECT PERMANENTLY LABEL UNIT ON ROOF. |
| 08/01/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*WIRE SMOKE DETECTOR INSTALL CONDENSATE DRAIN LINES. |
| 07/25/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE ACCESS TO BOTH SIDES OF AIR HANDLE FOR SERVICE REFER TO INSTALLATION INSTRUCTIONS. 2.) INSULATE ALL BARE METAL ON SUPPLY & RETURN DUCTS & PLENUMS. 3.) PROVIDE SECONDARY DRAIN PAN AS PER PLANS. 4.) INSTALL PRIMARY DRAIN 5.) FINISH INSTALLING SMOKE DETECTOR 6.) REPAIR INSULATION ON REFER LINES. |