Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK FOR TEMPORARY C OF O. CALL BACK FOR FINAL WHEN ELECTRICAN INSTALLS RETAINER CLIP ON MAIN 100AMP PANEL P AND FINISH PANEL SCHEDULE. |
| 08/10/2001 |
ELECTRIC - FINAL |
|
Approved |
|
| 08/07/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
1.) NEED A RETAINER CLIP TO SECURE MAIN C/B AT PANEL #B.THIS CLIP WILL SECURE THE BACKFED C/B FROM ACCIDENTAL PULL OUT. 2.) PARTIAL FINAL GRANTED PENDING TEST OF ELECTRICAL ONCE ENERGIZED BY TEP. |