Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02400
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
08/09/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O HOLD FINAL FOR 1.) APPROVED CHANGE ON AC & FAN COIL MOVE TO PNL 1 FROM PNL H, ALSO LOAD CHANGES 2.) ELECT WATER TO BE WORKING HAVE ELECTRIC CONTRACTOR TAPE ORANGE WIRE TO WHITE IN PANEL H AND DISCONNECT BELOW SINK 3.) IF WATER HEATER TO BE 277U - CHANGE 2 POLE CB IN PNL H. NOTE TO OCUPPANT KEEP CLEAR AREA IN FRONT OF PLANELS. | |
08/08/2001 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C OF O | |
08/07/2001 | ELECTRIC - FINAL | Partial Approval | 1.) CHANGE OUT MAIN C/B AT PNL. A TO 100AMP 2.) PROVIDE APPROVAL BY ENGINEER CORNELL FOR THE CHANGE OF FCU TO 208U 1PHASE AND THE ROOF MTD CONDENSOR TO 208V 3 PHASE NOW FED FROM PNL A. 4.) PROTECT MC CABLE IT CASH WRAP. | |
08/03/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) COUNTER INSTALL INCOMPLETE. |