Permit: T01CM02400

Parcel: 128010010

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02400

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/09/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O HOLD FINAL FOR 1.) APPROVED CHANGE ON AC & FAN COIL MOVE TO PNL 1 FROM PNL H, ALSO LOAD CHANGES 2.) ELECT WATER TO BE WORKING HAVE ELECTRIC CONTRACTOR TAPE ORANGE WIRE TO WHITE IN PANEL H AND DISCONNECT BELOW SINK 3.) IF WATER HEATER TO BE 277U - CHANGE 2 POLE CB IN PNL H. NOTE TO OCUPPANT KEEP CLEAR AREA IN FRONT OF PLANELS.
08/08/2001 ELECTRIC - FINAL Partial Approval OK FOR TEMP C OF O
08/07/2001 ELECTRIC - FINAL Partial Approval 1.) CHANGE OUT MAIN C/B AT PNL. A TO 100AMP 2.) PROVIDE APPROVAL BY ENGINEER CORNELL FOR THE CHANGE OF FCU TO 208U 1PHASE AND THE ROOF MTD CONDENSOR TO 208V 3 PHASE NOW FED FROM PNL A. 4.) PROTECT MC CABLE IT CASH WRAP.
08/03/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) COUNTER INSTALL INCOMPLETE.