Permit: T01CM02281

Parcel: 128010010

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/26/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*NEED TO SEE DUCT SMOKE DETECTOR WIRED. NOTE: PLAN DO NOT SHOW A SECONDARY DRAIN PAN UNDER AIR HANDLER CHECK WITH ARCHITECT FOR DIRECTION.
07/18/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) PROVIDE 1" CONDENSATE DRAIN FOR AIR HANDLER 2.) INSULATE RETURN DUCT. 3.) PROVIDE SMOKE DETECTOR IN RETURN DUCT. 4.) PROVIDE A THREADED PLUG IN UNUSED DRAIN OUTLET ON AIR HANDLER. LEAVE OUT CEILING TILES UNDER RETURN DUCT & AIR HANDLER.