Permit: T01CM02145

Parcel: 14122004H


Addresses:

8755 S RITA RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T01CM02145

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
07/10/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) SOME UNITS LEAKNG WATER ONTO THE ROOF 2.) PROVIDE BLOCKING UNDER DRAIN LINES. 3.) DIVERT WATER FROM UNDER STAIRS.
07/02/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*FINISH WORK ON ROOF TOP UNITS. REPAIR LEAKS IN WATER PIPING. NEED TO SEE SYSTEM.OK FOR TEMP C OF O.
06/17/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*AHU-1 & 2 WATER PIPES LEAKING, FINISH CONDENSATE TERMINATION RTU-4. NO CONDENSATE RTU-5 NO ACCESS,NO CONDENSATE RTU-6 AS ACCESS. NO CONDENSATE. ALL UNITS CONDENSATE CANNOT DISCHARGE IN FRONT OF SERVICE PANELS RTU-7 GAS PIPE IN FRONT SERVICE PANELS 4' CLEARANCE IS REQUIRED SECURE ELEC. DISCONNECT ON CONDENSOR SSC-2.
06/04/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*COMBUSTION AIR OK RUN 322. OK FOR CEILING TILES THROUGH OUT.
05/17/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*NEED TO ADDRESS EMERGENCY RELIEF VALVES FOR AMMONIA DISCHARGE TANK OK TO CHARGE AMMONIA SYSTEM. OK FOR CEILING TILES IN ROOM 451,452,429,431 424,422,425,401,305,320,316,318. SEAL OPENING IN PLENUM CEILING COMPUTER ROOM 423. NEED LOW COMBUSTION AIR IN EQUIPMENT ROOM 322.
03/14/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* ADD HANGERS ON PIPING AS NEEDED. WILL DO HYDRO TEST ON NEXT VISIT.