Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T01CM02145
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
05/30/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK FOR CEILING TILES ROOMS 514 & 515 WHERE IS MAKE UP AIR? ROOM 510 & 511 WHERE IS RETURN AIR IN CEILING? ROOM 506, 507,508,509 MISSING RETURN AIR. | |
05/23/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK FOR CEILING TILES IN ROOMS 319,402,403,415,417,418,426,450 454,459, STILL NEED TO SEE TRUCKERS LOUNGE & ROOM 421 & CONTROL ROOM. | |
05/17/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
05/16/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK FOR CEILING TILES ROOM 457,460,456,458,455,419,444,306,307,308,309,310,312,324,318,321,323,317,315. | |
05/13/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK FOR CEILING TILES ROOMS 441, 445,446,447,448,428,440,443 MAIN CORRIDOR, HALLWAYS TO OFFICE PROVIDE ANGLE IRON ON FIRE DAMPER IN RECORDS ROOM. NEED TO SEE WIRING ON FIRE/SMOKE DAMPERS. | |
05/09/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK FOR CEILING TILES IN ROOMS 304,301,303,406,409,414,413,404,410,418,417,437,436,432,435,433 CHECKED FIRE DAMPERS OK FOR ANGELS RTU-7 DUCT & FIRE DAMPER OK. | |
04/18/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*FIRE DAMPERS OK IN TRASH ROOM STILL NEED TO SEE ALL OTHER DAMPERS. | |
03/27/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTION ON STAINLESS STEEL DUCTS TO AH 1 & 2 OK TO INSULATE. | |
03/20/2002 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* | |
03/13/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTED LOCKER ROOM EXHAUST SHAFTS OK TO COVER DUCT IS COMPUTER ROOM IS OK PROVIDE LISTING FOR FIRE DAMPERS & SMOKE DAMPERS. | |
03/12/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* PARTIAL INSPECTION ON STAINLESS STEEL DUCT ON AH-2 SUPPLYDUCT ON NORTH END UP TO DROPS OK TO INSULATE. | |
03/01/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTED SUSPENDED ROUGH DUCT IN AREA 13 TRUCKERS LOUNGE OK TO PROCEED WITH INSULATION CHECKED DUCT SMOKE DETECTOR. | |
02/22/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTED SUPPLY & RETURN WATER SYSTEM FROM COOLING TOWER TO AIR COMPRESSOR & MOISTURED DRYERS TEST IS OK. | |
02/21/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
02/20/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | DISCUSSED EXHAUST SYS DUCT. PERSONELL LOCKERS UP THRU ROOF. HAVE ENGINEER PROVIDE DIRECTION W/DETAIL. | |
01/30/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OVERHEAD HORIZONTAL PIPING HANGERS NOT SPACED MAX. 10' AS PER CODE. PIPING HANGERS ARE SPACED 12' BECAUSE OF TRUSS SPACING. TRUSSSES ARE EVERY 6'.USED OVERSIZE ALL THREAD INSPECTED GRAVITY CONDENSATE FOR STEAM RECOVERY IN AREA 5 OVERHEAD AND OVER TO STORK PIT. STILL NEED TO SEE FINAL CONNECTIONS TO HOLDING VESSEL PRESSURE TEST FOR OVERHEAD AT 100PSI. OK TO INSULATE. SPEC. LOOK CALLS FOR MAX 15' SPACING ON OVERHEAD PIPES. |