Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/28/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) SUPPORT CONDUIT AND FLEX AND M/C CABLE AS PER CODE. 2.) USE BREAKER AS APPROVED BY MANUFACTURE 3.) FLU ALL USED OPENING. |
| 07/27/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/26/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/26/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 07/25/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*RECEIVED CH#13508 |