Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/28/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/27/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) SUPPORT CONDUIT AND FLEX AND M/C CABLE AS PER CODE. 2.) USE BREAKER AS APPROVED BY MANUFACTURE 3.) FLU ALL USUSED OPENING 4.) CK M/C FITTINGS. |
| 07/26/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) ATTACH FIXTURES TO GRID.2.) NEED SUPPORT WIRES TO TRAC AT CLIPS. 3.) SUPPORT M/C CABLE AS PER CODE WITHIN 12" OF BOXES 4.) SUPPORT CONDUIT WITHIN 3' OF BOXES. |
| 07/25/2001 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |