Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM02082

Parcel: 10602001C


Addresses:

3964 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM02082

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/27/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) SUPPORT CONDUIT AND FLEX AND M/C CABLE AS PER CODE. 2.) USE BREAKER AS APPROVED BY MANUFACTURE 3.) FLU ALL USUSED OPENING 4.) CK M/C FITTINGS.
07/26/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) ATTACH FIXTURES TO GRID.2.) NEED SUPPORT WIRES TO TRAC AT CLIPS. 3.) SUPPORT M/C CABLE AS PER CODE WITHIN 12" OF BOXES 4.) SUPPORT CONDUIT WITHIN 3' OF BOXES.
07/25/2001 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*