Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM02082
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/27/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) SUPPORT CONDUIT AND FLEX AND M/C CABLE AS PER CODE. 2.) USE BREAKER AS APPROVED BY MANUFACTURE 3.) FLU ALL USUSED OPENING 4.) CK M/C FITTINGS. | |
07/26/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) ATTACH FIXTURES TO GRID.2.) NEED SUPPORT WIRES TO TRAC AT CLIPS. 3.) SUPPORT M/C CABLE AS PER CODE WITHIN 12" OF BOXES 4.) SUPPORT CONDUIT WITHIN 3' OF BOXES. | |
07/25/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* |