Permit: T01CM01835

Parcel: 131041270


Addresses:

5033 E 25TH ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/24/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
09/13/2001 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) GROUNDING SYSTEM IS DISCONNECTED (RECONNECT ASAP) 2) NEED GAS DEMAND FOR HOUSE, LENGTHS OF PIPE RUNS 3) HOLES CUT IN 2 X RAFTERS TO BIG, TO CLOSE TENSION SIDE OF RAFTER, SHEET TO EXPLAIN LEFT WITH PLAN 4) LEAVE FLEX GAS LINE INSTALLATION INSTRUCTIONS ON SITE 5) EXISTING BATHROOM WILL NEED AND EXHASUT FAN 6) TAKE THE WEIGHT OF 2 X 4 WALL (AT REAR DOOR) NO HEADER INSTALLED 7) NO GRD WATER BOND, GAS BOND RISER AT SERVICE PANEL 8) NEED A GAS PRESSURE TEST 9) ALL TRADES REQUIRED TO BE COMPLETE/APPROVED BEFORE FRAMING CAN BE APPROVED