Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2001 |
ELECTRIC - FINAL |
|
Approved |
|
| 08/06/2001 |
ELECTRIC - FINAL |
|
Denied |
I.D. ALL DISCONNECTS SERVICE SWITCHES EQUIPMENT DISCONNECTS ETC. 2.) THE FEEDER CABLES FROM THE MAIN METER SWITCH ARE NOT SIZED PER PLAN.PLAN CALLS FOR 3/0 CU THE INSTALLED SIZE IS 1/0. INSTALL CORRECT SIZE OR FURNISH A REVISED PLAN APPROVED BY TEH ENGINEER AND THE CITY OF TUCSON PLANS EXAMINER. |