Permit: T01CM01586

Parcel: 128010010

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T01CM01586

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2001 MECHANICAL - HOODS Approved
07/27/2001 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*WIRE DUCT SMOKE DETECTOR TO INTERUPT FAN OPERATION. RELCOATE ELECTRICAL FLEX CONDUIT AWAY FROM FILTER ACCESS.
07/25/2001 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*CONDENSATE DRAIN DOES NOT HAVE ADEQUATE SLOPE. NIPPLE IS CROSSTHREADED SLOPE 1/8" PER FOOT. WIRE DUCT SMOKE DETECTOR TO FAN COIL. CLEANOUT DOOR NOT ACCESSIBLE.
07/23/2001 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*OK FOR SECOND LAYER OF WRAP ON GREASE DUCT. OK FOR CEILING TILES LEAVE OUT AROUND HOOD.
07/19/2001 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*