Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 01/22/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*1.) SUPPORT CONDUIT AS PER CODE FRONT PORCH 2.) YOU WILL NEED BONDING DEVICES AT THE SERVICE ON THE NIPPLE BETWEEN THE CT CAN AND GUTTER ON BOTH SIDES 250-94. 3.) GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO GROUNDED CONDUCTOR AT THE SERVICE 250-24. 4.) PLEASE CLEAN THE SURFACE BEHIND THE GROUND LUG IN THE GUTTER 250-12.5.) THERE IS DOUBLE LUGING FOR THE LAY LUGS ONTHE BOND BUSHINGS, AND THE LUGS IN THE DISCONNECTS. 6.) PLEASE LABEL PUMP (COVER) DISCONNECTS 7.) NEED TO PROVIDE WORKING CLEARENCE IN FRONT OF A/C DISCONNECT (HR1) 110-26 8.) CORD TO BE FULLY INTO CORD CAP ON COOLER CORD. 9.) WILL NEED TO SEE THE CUT SHEET FOR THE OUTSIDE LIGHTS AS PER PLANS. |