Permit: T01CM01513

Parcel: 10611021F


Addresses:

3301 N FREEWAY

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/24/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
01/22/2002 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*1.) SUPPORT CONDUIT AS PER CODE FRONT PORCH 2.) YOU WILL NEED BONDING DEVICES AT THE SERVICE ON THE NIPPLE BETWEEN THE CT CAN AND GUTTER ON BOTH SIDES 250-94. 3.) GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO GROUNDED CONDUCTOR AT THE SERVICE 250-24. 4.) PLEASE CLEAN THE SURFACE BEHIND THE GROUND LUG IN THE GUTTER 250-12.5.) THERE IS DOUBLE LUGING FOR THE LAY LUGS ONTHE BOND BUSHINGS, AND THE LUGS IN THE DISCONNECTS. 6.) PLEASE LABEL PUMP (COVER) DISCONNECTS 7.) NEED TO PROVIDE WORKING CLEARENCE IN FRONT OF A/C DISCONNECT (HR1) 110-26 8.) CORD TO BE FULLY INTO CORD CAP ON COOLER CORD. 9.) WILL NEED TO SEE THE CUT SHEET FOR THE OUTSIDE LIGHTS AS PER PLANS.