Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/14/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*OK TO TILE. |
| 01/13/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) CONDUIT & DATA TO BE SUPPORTED AT BOTH ENDS 300-11. ALSO IDEPENDANT OF CEILING WIRES 2.) CONDUIT TO BE SUPPORTED AS PER CODE (3/4" CONDUIT ABOVE PANEL.) |
| 01/09/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) ELECTRIC & DATA TO BE INDEPENENLY SUPPORTED 300-11 CAN NOT USE CIELING SUPPORT WIRES. 2.) PLEASE ATTACH FIXTURE TO GRID IF USEING CLIPS THEY MUST HOLD FIXTURE TO GRID. 3.) FINISH BOX MAKE-UP AND INSTALL MISSING COVERS 4.) CONDUIT TO BE SUPPORTED AS PER CODE 348. |