Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* OK TO COVER |
| 03/19/2001 |
PLUMBING - INTERMEDIATE |
|