Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00807
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
04/06/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920*BLDG LOCKED | |
04/04/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1) LOOSE TIES NOT SUPPORTING CABLE. TIE MC EVERY 6' 2) BOXES TO BE FULLY MADE UP INCLUDING GROUNDING 3) PLEASE USE APPROVED METHOD AND MATERIAL TO SECURE ROMEX EG-TY RAPS 4) ISOLATE GROUNDING IN SUB PANEL 5) PLEASE COVER SUB PANEL COMPLETELY TO AVOID CONTAMINATION OF BUYSSING FROM FOREIGN DEBRIS 6) PLAN HAS 2" CONDUIT AT #3 CU. CODUCTION FOR PANEL FEEDER. HAVE APPROVED REVISION BEFORE FINAL INSP. FOR THE SUBSTITUTION OF #2 CU, ROMEX 7) SOME BOXES OVER FILLED. SEE 4 SQ BOXES IN BATHROOM AREAS 8) MISSING PLASTER RING |
|
03/22/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0240* | |
03/19/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920* LOCKED NO ACCESS |