Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00804
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2001 | ELECTRIC - FINAL | Approved | ||
07/11/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*2 SEISMIC TIES REQUIRED FOR EACH FIXTURE 2 SCREW THOUGH "T" BAR TO EACH FIXTURE, AT ENDS SUPPORT M.C. CABLE WITHIN 12" OF BOX AND EVERY 6FT. NEED DISCONNECT SWITCH FOR WATER HEATER OR OTHER EFFECTIVE MEANS. NEED TO HAVE METAL EMBOSSED TAPE OR ENGRAVED METAL TAGS FOR SERVICE ADDRESS AND DISCONNECT NUMBER. |