Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00803
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2001 | ELECTRIC - FINAL | Approved | ||
07/11/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*2 SEISMIC TIES REQUIRED FOR EACH FIXT, 1 SCREW THROUGH T BAR TO EACH FIXT. ATENDS SUPPORT M.C. CABLE WITHIN 12" OF BOX AND EVERY 6TH. NEED DISCOUNT SWITCH FOR WATER HEAT OR OTHER APPROVED MEANS. NEED TO HAVE METAL EMBOSSED TAPE OR ENGRAVED METAL TAGS FOR SERVICE ADDRESS AND DISCONNECT NUMBER. |