Permit: T01CM00803

Parcel: 137090090


Addresses:

5452 S 12TH AV #100

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/13/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/06/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*BLDG LOCKED
04/04/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* 1) LOOSE TIES NOT SUPPORTING CABLE. TIE MC EVERY 6' 2) BOXES TO BE FULLY MADE UP INCLUDING GROUNDING
3) PLEASE USE APPROVED METHOD AND MATERIAL TO SECURE ROMEX EG-TY RAPS 4) ISOLATE GROUNDING IN SUB PANEL 5) PLEASE COVER SUB PANEL COMPLETELY TO AVOID CONTAMINATION OF BUYSSING FROM FOREIGN DEBRIS 6) PLAN HAS 2" CONDUIT AT #3 CU. CODUCTION FOR PANEL FEEDER.
HAVE APPROVED REVISION BEFORE FINAL INSP. FOR THE SUBSTITUTION OF #2 CU, ROMEX 7) SOME BOXES OVER FILLED. SEE 4 SQ BOXES IN BATHROOM AREAS 8) MISSING PLASTER RING
03/22/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0240* 1) THE MC CABLE MUST BE FIRMLY SUPPORTED WITHIN 12" OF EACK BOX 2) THE 2X2 STUD WALLS WILL REQUIRE NAIL PLATES WHERE THE MC CABLE IS WITHIN 1 1/4" OF THE SURFACE OF THE STUD
03/19/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920* LOCKED NO ACCESS