Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000*100,120,140,160,180 T01CM00809 T01CM00807 T01CM00803 T01CM00806 T01CM00804 |
|
| 08/20/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*CIELING GRID NOT HUNG PER UBC STANDARDS. USE #12 WIRE. START 8" FROM WALL AND THEN HANG EVERY 4' O.C. PERIMETER WIRES TO BE 8" FROM ALL WALLS ON ALL CROSS RUNNERS AND MAIN RUNNERS. |