Permit: T01CM00637

Parcel: 107131890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/24/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/31/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*NOTES BLD # UNITS 6101 6102
08/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) CONDUCTOR RUN BETWEEN FIXTURE AND DRY WALL ALL UNITS HAVE ALL FIXTURES OPEN FOR INSPECTION BATH BARS. A REFEE WILL BE ASSESSED IF NOT COMPLETE NEXT INSPECTION.
08/27/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. FILL UNUSED OPENING A/C DDISCONNECT # 6102 2. STRAP WATER HEATER FLEX AFTER COUPLING # 6102 & 6201 3. EXPOSED TO DRYWALL, CONDUCTORS # 6202 & 6201 4. PROTECT SEALTITE UPON PASSING THRU JUNCTION BOX.