Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM00412
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
04/19/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES: NEW WALL BLD 'E' 1. SUPPORT MC CABLE WITHIN 12" EACH BOX OR DEVICE, 334-10 NEC 2. INSTALL GROULD PIGTAILS EACH DEVICE BOX 370-4 NEC | |
03/05/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* BLDG E POWER PANELS AND TRANSFORMER OK |