Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/11/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/08/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) INCREASE THE TENSION SO GARAGE PEDESTRIAN DOOR SELF CLOSES AND LATCHES 2) GAS TO MASTER FIREPLACE NOT HOOKED UP 3) MOVE NORTH A/C UNIT'S EXTERIOR DISCONNECT TO CORENER OF HOUSE, SO THERE IS 30" CLEARANCE 4) SEAL KNOCKOUT HOLE IN BOTTOM OF MAIN PANEL INSPECTOR NOTE: CHECK ANTI-TIP AFTER STOVE IS INSTALLED |